Replacing A Differential Pressure Switch - Huawei FusionCol8000-C210 User Manual

In-room chilled water smart cooling product
Hide thumbs Also See for FusionCol8000-C210:
Table of Contents

Advertisement

FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Netherland GS)
Figure 10-1 Removing the air filter
Step 2 Install a new air filter based on the airflow direction, push the baffle plate, press
and rotate the spring pin to secure the air filter, and tighten the screws on the
disassembly tab.
Step 3 On the home screen, choose Maintenance > Performance to enter the
Performance Maintenance screen and clear the runtime of the air filter.
----End

10.2 Replacing a Differential Pressure Switch

Context
Tool: Phillips screwdriver
Procedure
Step 1 Tap Shutdown on the home screen of the display module.
Exercise caution because the unit is still energized after it is shut down on the
screen of the display module.
Step 2 Open the electric control box, turn off the active power switch QF1 and standby
power switch QF2, and remove the air filter in the middle.