Procedure
Step 1 Remove the top hole cover.
Step 2 Knock off the knock-out holes for the chilled water inlet and outlet pipes.
Step 3 Connect the chilled water inlet and outlet pipes.
Figure 4-18 Connecting the chilled water inlet and outlet pipes
1.
2.
3.
Step 4 Connect the water valve actuator to the chilled water outlet pipe of the unit.
Step 5 Attach thermal insulation foam to the pipes and ensure that the foam is in close
contact with the pipes.
Issue 01 (2022-12-30)
NO TE
Prevent impurities from entering water pipes and the unit.
Remove the water pipe plug using a 70# open-end wrench and 36# open-end
wrench (the 70# open-end wrench is used to hold the water pipe nut and the
36# open-end wrench is used to hold the plug to prevent the pipe from being
distorted).
Apply thread sealant to the external screw threads of the external pipe or
wrap the pipe with sealing tape.
Use a 70# open-end wrench and 18# pipe wrench to connect the water pipe.
NO TE
● Ensure that the arrow direction on the water valve actuator is consistent with the water
flow direction.
● The distance between the water valve actuator and the unit must be less than or equal
to 2 m.