Step 3 Connect the differential pressure sensor cables to terminals 4, 5, and 6 of X502.
----End

4.10 (Optional) Connecting a Point-Type Water Sensor

Context
This section describes how to connect a water sensor. A water detection cable can
also be connected.
A water sensor monitors resistance changes at terminals to determine whether
the floor is watery. When the terminals of a water sensor detect water or other
conductive liquid, resistance between the two terminals decreases. Keep water
sensors far away from water traps or floor drains.
Procedure
Step 1 Connect one end of the water sensor cable to the water sensor.
Step 2 Connect the other end of the water sensor cable to the signal terminals 1 and 2 of
X502 through the bottom of the cabinet.
Figure 4-36 Connecting the water sensor
Issue 01 (2022-12-30)
Connect a pressure inlet tube to the + mark and route it to the positive
pressure area of the equipment room through the hole on the top of the
cabinet. Ensure that the pressure inlet faces downwards.
Connect a pressure inlet tube to the – mark and route it to the air return side
on the top of the cabinet through the hole atop. Ensure that the pressure inlet
faces downwards.