FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Netherland GS)
Communications Ports
●
●
●
●
Appeara
nce
●
Appearance
Issue 01 (2022-12-30)
FE_1 and FE_2 ports: connect FE (MAC_CAN) teamwork communications
cables.
CAN_IN and CAN_OUT ports: connect CAN teamwork and RS485 monitoring
cascading communications cables.
RS485/12V port: connects a temperature and humidity (T/H) sensor.
COM/FE port: connects a monitoring communications cable.
Pin
FE_1
and
FE_2
PIN1
FE TX+
PIN2
FE TX–
PIN3
FE RX+
PIN4
-
PIN5
-
PIN6
FE RX–
PIN7
-
PIN8
-
USB port: connects a WiFi module or USB flash drive.
NO TE
This port is protected by a security mechanism.
USB Port
● Connects the WiFi module to the unit over the app. You
can obtain the service authorization code when the unit
is powered on for the first time, and view or obtain the
running information about the unit during inspection.
The user must be an authorized service engineer. To
ensure security, remove the WiFi module immediately
after use.
● Connects a USB flash drive to export data, import and
export configuration files, import certificates and keys,
and upgrade the version.
Copyright © Huawei Digital Power Technologies Co., Ltd.
CAN_IN
CAN_OU
T
RS485-N
RS485-N
+
+_1
RS485-
RS485-
N-
N-_1
-
-
RS485-N
RS485-N
+
+_1
RS485-
RS485-
N-
N-_1
-
-
CANH
CANH
CANL
CANL
2 Product Composition
RS485/12V
COM/FE
Port
Port
RS485 HT+
FE TX+
RS485 HT–
FE TX–
12V
FE RX+
RS485 HT+
RS485-N
+_2
RS485 HT–
RS485-N-
_2
-
FE RX–
-
-
GND
-
24