4.2.2.4 Cable
● The onsite grounding resistance must comply with related standards.
● Select power cables with appropriate diameters based on the maximum
working currents.
When connecting cables, fit them with protective hoses.
Table 4-1 Cable specifications
Item
Active/standby
power cable
Equipotential ground
cable
T/H sensor cable,
teamwork control
cable, and
monitoring
communications
cable
Water valve actuator
signal cable
(Optional) Cable-
type water sensor
cable
4.3 Installing a Unit
Issue 01 (2022-12-30)
NO TE
● The height of a U-shaped pipe clamp equals the diameter of the pipe with thermal
insulation foam minus 5 mm. The pipe supports are to be purchased.
● Stainless steel 304 is recommended for pipe supports and pipe clamps.
● Install a support every 2500 mm in the straight sections of pipes, and 1000 mm away
from each bending point in the turning section.
NO TICE
Specifications
Electronic|Electric Cable, 600 V/1000 V, ZA-RVV, 4 x 6
mm
Outdoor copper cable with a cross-sectional area of at
least 6 mm
Cat 5e or higher shielded network cable
UL2464 300V 20AWGx4C
CAT 5e or higher shielded network cable. Recommended
length: ≥ 4 m
Copyright © Huawei Digital Power Technologies Co., Ltd.
2
, Black (4 Cores), Outdoor Cable, CE
2