FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Netherland GS)
Step 2 Secure the air duct to the top of the unit using M4x12 screws and flat washers,
and secure the two sides of the air duct to the two sides of the unit using M6x25
screws.
Figure 4-15 Securing an air duct (unit: mm)
(1) Maintenance door
If an air duct is used at the air supply side, the maintenance space requirements of
devices such as fans must be considered. The maintenance door is shown in (1) of
the preceding figure. The recommended dimensions are 417 mm x 1226 mm.
----End
4.4 Connecting Pipelines
4.4.1 Connecting a Drainpipe
Issue 01 (2022-12-30)
CA UTION
NO TE
● If the equipment is to be secured to the floor, place the bottom of the air duct on the
floor and use anchor baffle plates to secure the air duct.
● If the equipment is to be secured to the base, it is recommended that you install baffle
plates on the base before securing the bottom of the air duct.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 System Installation
47