Procedure
● If the cable-type water sensor is in direct contact with metal, a false alarm may
be generated. Therefore, avoid direct contact with metal during installation. Do
not secure the water detection cable using a metal fastener or bind the cable
to a metal pole. You are advised to use a winding pipe to wrap the water
detection cable. The recommended size is φ20 mm.
● The cable-type water sensor should be installed in a dry environment without
condensation. Do not route the water detection cable in areas that are prone to
rain, vapor, or long-term high humidity.
● Keep the product away from corrosive environments such as acid, sulfur, and
salt. Do not install the water detection cable in a dust-prone area.
● The lead wire must be fixed to ensure that the connector is not stressed.
● Keep the water detection cable away from sharp objects to prevent scratches.
● Do not throw away the plug at the end of the extension cable. Install the plug
at the end of the water detection cable for protection.
Step 1 Determine a proper position near the smart cooling product and install the water
detector using M4 screws.
Step 2 Connect the water detection cable to the conversion cable.
Figure 4-38 Connecting cables
(1) Conversion cable end B, connecting to the
water detection cable
Step 3 Connect the other end of the conversion cable to the water detector.
Issue 01 (2022-12-30)
NO TE
The water detection cable can be connected using a quick-connect terminal and extended
flexibly.
NO TICE
NO TE
Do not install the water detector on or inside a smart cooling product cabinet.
NO TE
The water detection cable and conversion cable are interconnected through male and
female connectors.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 System Installation
(2) Water detection cable end A, connecting to
the conversion cable