Pattern Setting screen
Editing a time pattern
Click the time pattern you intend to edit.
The set start time is displayed.
The setting state is displayed. Perform editing.
At the end of editing, click the [Update] button.
At the end of setting, click one of the following buttons:
[OK] button: Saves the set contents and closes the Pattern Setting screen.
[Apply] button: Saves the set contents. The Pattern Setting screen remains unchanged.
Note
When Start/Stop, operation mode setting, room temp. setting, fan speed setting, air flow direction set-
ting, swing setting, economy mode, and anti freeze setting are changed frequently by using the central
controller like BMS, System Controller Lite, touch panel controller, etc., the number of operations for each
indoor unit must not exceed 7,500 times/year.
If the number of setting change exceeds the above specified number, the rewriting frequency of the
EEPROM (built into the air conditioner and used for setting memory) will be exceeded, and may cause
breakdown.
Copyright© 2013-2015 Fujitsu General Limited. All rights reserved.
Pattern Setting screen opens.
Creating a new time pattern
Set the control start time.
Make the necessary operation settings.
→ See par. 18-3-3 Operation pattern setting
items
At the end of the necessary operation set-
tings, click the [Add] button.
Check that the pattern was added to the time
pattern.