Melsec-Fx - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

20.4.2
Communication detail settings
Make the settings according to the usage environment.
■1. Serial (MELSEC)
Item
Transmission Speed
Retry
Timeout Time
Delay Time
*1
Format
*1
■2. MELSEC-FX
Item
Transmission Speed
Retry
Timeout Time
Delay Time
20 - 16
20.4 GOT Side Settings
Set this item when change the transmission speed used for communication with the
connected equipment. (Default: 115200bps)
When the setting exceeds the limit of the connected equipment, communication is
performed at the fastest transmission speed supported by the connected equipment.
Set the number of retries to be performed when a communication error occurs.
(Default: 0time)
Set the time period for a communication to time out. (Default: 3sec)
Set this item to adjust the transmission timing of the communication request from the
GOT. (Default: 0ms)
Set the communication format. (Default: 1)
The format setting differs depending on the controller.
L6ADP-R4 adapter: [2]
Other than L6ADP-R4 adapter: [1]
Set this item when change the transmission speed used for communication with the
connected equipment. (Default: 115200bps)
When the setting exceeds the limit of the connected equipment, communication is
performed at the fastest transmission speed supported by the connected equipment.
Set the number of retries to be performed when a communication error occurs.
(Default: 0time)
Set the time period for a communication to time out. (Default: 3sec)
Set this item to adjust the transmission timing of the communication request from the
GOT. (Default: 0ms)
Description
Description
Range
9600bps, 19200bps,
38400bps, 57600bps,
115200bps
0 to 5times
3 to 30sec
0 to 300 (ms)
1, 2
Range
9600bps, 19200bps,
38400bps, 57600bps,
115200bps
0 to 5times
1 to 30sec
0 to 300 (ms)