■4. Ethernet setting
Item
Host
N/W No.
*1
Station
Unit Type
IP Address
Port No.
Communication
*1
Each of [GOT Station] set in the communication detail setting and [Station] set in the Ethernet setting must be set to different
station numbers.
➠ ■2.
The host is displayed. (The host is indicated with an asterisk (*).)
Set the network No. of the connected Ethernet module.
(Default: blank)
Set the station No. of the connected Ethernet module.
(Default: blank)
FREQROL (fixed)
Set the IP address of the connected Ethernet module.
(Default: blank)
Set the port No. of the connected Ethernet module.
(Default: 5008)
UDP, TCP
(Default: UDP)
Communication detail settings
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be changed on the Utility's [Communication setting]
after writing [Controller Setting] of project data.
For details on the Utility, refer to the following manual.
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the Utility, the latest setting is effective.
Description
14.3 Ethernet Connection
Set value
-
1 to 239
1 to 120
FREQROL (fixed)
Inverter side IP address
Inverter side port No.
Adjust the settings with the Inverter
settings.
14 - 49