Mitsubishi Electric GOT2000 Series Connection Manual page 313

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(3) Ethernet setting
Ethernet setting No.1
*1
Set the same value as that of GOT N/W No.
*2
Set a value different from that of the GOT PLC No. and the PLC No. of other PLCs on the same network.
*3
The following [Port No.] and [Communication format] can also be set.
[Port No.]: 5007
[Communication]: TCP
■4. Checking communication state of C Controller module (MELSEC iQ-R Series)
(1) When using the Command Prompt of Windows.
Execute a Ping command at the Command Prompt of Windows.
(a)
When normal communication
C:\>Ping 192.168.3.3
Reply from 192.168.3.3: bytes=32 time
<10ms TTL=32
(b)
When abnormal communication
C:\>Ping 192.168.3.3
Request timed out.
(2) When abnormal communication
At abnormal communication, check the following and execute the Ping command again.
• Cable connecting condition
• Confirmation of switch and network parameter setting
• Operation state of PLC CPU (faulty or not)
• The IP address of C Controller module (MELSEC iQ-R Series) specified in the ping command
Item
Host
N/W No.
PLC No.
Type
IP Address
*3
Port No.
*3
Communication
POINT
POINT
POINT
Ethernet diagnostics of CW Configurator
Ethernet diagnostics of CW Configurator is available to a Ping test from the PLC.
For details of Ethernet diagnostics of CW Configurator, refer to the following manual.
Manuals of C Controller module (MELSEC iQ-R Series)
Set value
*
*1
1
*2
2
RnCCPU
192.168.3.13
5006
UDP
5.4 PLC Side Setting
-
*1
1
*2
3
RnCCPU
192.168.3.4
5006
UDP
5
5 - 47