CC-Link System Access Range for Monitoring

■1. When using Bus connection/CPU direct connection/serial communication connection
Only connected stations can be monitored.
■2. When using CC-Link connection (intelligent device station)
(1) Access range
The master station and local station can be monitored.
Monitor target
Master station (Remote network Ver.2 mode)
Local station Station No.1 (Ver.1 compatible)
Local station Station No.6 (Ver.2 compatible)
*1
Monitoring is available only when the CC-Link communication module is the GT15-J61BT13.
All devices RX, RY, RWw and RWr that are allocated to the master station by the CC-Link parameter setting can be
monitored.
When the monitor target is the multi-PLC system, CPU No. 1 to No. 4 can be monitored.
The device range of RX, RY, RWw, RWr to be allocated to the GOT differs according to the setting of the number of
CC-Link communication units (one station/four station) occupied.
For details on the number of CC-Link stations occupied, refer to the following manual .
User's manual of the CC-Link master unit to be connected
(2) Setting device name and device number
(a)
Monitoring devices RX, RY, RWw and RWr that are allocated to the master station by CC-Link
parameter setting
Use the following device names.
For devices RX, RY, RWw and RWr, designate the addresses allocated by station number setting.
• In the case of CC-Link Ver.2 (Device names to be refreshed automatically are indicated as X, Y, and D.)
Device name on PLC CPU
Input
Output
Register (write area)
Register (read area)
• In the case of CC-Link Ver.1 (Device names to be refreshed automatically are indicated as X, Y, and D.)
Device name on PLC CPU
Input
Output
Register (write area)
Register (read area)
(b)
Monitoring PLC CPU devices of other stations
Set the device name and device No.
2.DEVICE RANGE THAT CAN BE SET
Monitoring by cyclic transmission
Automatic
Device name on master station
refresh
X
Remote input
Y
Remote output
Remote register (write
D
area)
Remote register (read
D
area)
Automatic
Device name on master station
refresh
X
Remote input
Y
Remote output
Remote register (write
D
area)
Remote register (read
D
area)
3.3 CC-Link System Access Range for Monitoring
: Can be monitored,
Monitoring by transient transmission
*1
GT Designer3 settings
Link
scan
Device name
RX
X
RY
Y
RWw
Ww
RWr
Wr
GT Designer3 settings
Link
scan
Device name
RX
X
RY
Y
RWw
Ww
RWr
Wr
3
: Cannot be monitored
Set device range
X0 to X1FFF
Y0 to Y1FFF
Ww0 to Ww7FF
Wr0 to Wr7FF
Set device range
X0 to X7FF
Y0 to Y7FF
Ww0 to WwFF
Wr0 to WrFF
3 - 15