Mitsubishi Electric GOT2000 Series Connection Manual page 338

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(2) GOT Standard Ethernet Setting
GOT IP Address
Subnet Mask
Default Gateway
Peripheral Communication Port No.
Transparent Port No.
(3) Ethernet setting
Ethernet setting No.1
*1
*2
*3
■4. Checking communication state of C Controller module (Q Series)
(1) When using the Command Prompt of Windows.
Execute a Ping command at the Command Prompt of Windows.
(a)
When normal communication
C:\>Ping 192.168.3.1
Reply from 192.168.3.1: bytes=32 time
<10ms TTL=32
(b)
When abnormal communication
C:\>Ping 192.168.3.1
Request timed out.
(2) When abnormal communication
At abnormal communication, check the followings and execute the Ping command again.
• Cable connecting condition
• Confirmation of switch and network parameter setting
• Operation state of PLC CPU (faulty or not)
• The IP address of C Controller module (Q Series) specified in the ping command
5 - 72
5.4 PLC Side Setting
Item
Item
Host
N/W No.
PLC No.
Type
IP address
*3
Port No.
Communication
Set the same value as that of GOT N/W No.
Set a value different from that of the GOT PLC No. and the PLC No. of other PLCs on the same network.
The following [Port No.] and [Communication format] can also be set.
[Port No.]: 5007
[Communication]: TCP
QnD(H)CCPU
*3
Set value (Use default value)
192.168.3.18
255.255.255.0
0.0.0.0
5015
5014
Set value
*
*1
1
*2
2
192.168.3.1
5006
UDP
-
*1
1
*2
3
QnD(H)CCPU
192.168.3.2
5006
UDP