5.4.12

Connecting to Ethernet module (FX Series)

This section describes the settings of the GOT and Ethernet module (FX Series) in the following case of the system
configuration.
■1. System configuration
*1
These setting items do not exist at the PLC side. However, the virtual values must be set on the GOT side.
■2. Ethernet parameter settings of FX3U-ENET-L Configuration tool
(1) Ethernet settings
Set the Ethernet parameter with FX3U-ENET-L Configuration tool.
For using FX3U-ENET-L Configuration tool, install GX Developer Ver. 8.88S or later on the personal computer.
For details on FX3U-ENET-L Configuration tool, refer to the following manual.
FX3U-ENET-L Configuration tool
Item
Module
Operational settings
Initial settings
Open settings
POINT
POINT
POINT
Ethernet module (FX Series)
For details of the Ethernet module (FX Series), refer to the following manual.
FX3U-ENET-L User's manual
FX3U-ENET-ADP User's manual
<Ethernet module> (The settings other than the
following are set to the default)
Network No.
PC No.
IP address
Port No.
Communication
format
■4. [Controller Setting] and [Ethernet] of GT Designer3
<GOT>
(The settings other than the
following are set to the default)
PLC No.
: 1
IP address
: 192.168.3.18
Port No.
: 5019
Communication
: TCP (fixed)
format
*1
: 1 (virtual)
*1
: 2 (virtual)
: 192.168.3.19
: 5556 (fixed)
: TCP (fixed)
Setting
*1
Module 0
Refer to (2)
(Use default value.)
Refer to (3)
5.4 PLC Side Setting
Setting
(with GOT connected)
5 - 83
5