Mitsubishi Electric GOT2000 Series Connection Manual page 297

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

■2. GOT Side Communication format is TCP
(1) System configuration
For connecting one Built-in Ethernet port CPU to one GOT, the PLC side settings are not required. Set [Ethernet] for
[Controller Setting] on GT Designer3, and then connect Built-in Ethernet port CPU to the GOT.
*1
For the settings when using system devices including a hub and a transceiver, refer to the following.
*2
These setting items do not exist at the PLC side. However, the virtual values must be set on the GOT side.
(2) [Module parameter] of GX Works3
(a)
Built-in Ethernet port
Item
IP Address
Subnet Mask
Default Gateway
Communication data code
External Device Configuration
<Built-in Ethernet port CPU>
(Use the default value for settings other
than the following.)
Network No. :1 (virtual)
PLC No. :2 (virtual)
IP address :192.168.3.39
5.4.7 Connecting to MELSEC-Q/L Series built-in Ethernet port CPU (multiple connection)
■(3) [Controller Setting] and [Ethernet] of GT Designer3
(b) External Device Configuration
<GOT>
(Use the default value for settings other
than the following.)
Network No. :1
PLC No. :1
IP address :192.168.3.18
Port No. :5001
Communication format :TCP (fixed)
*1
*2
*2
Set value
192.168.3.39
(Use default value)
-
-
(Use default value)
○: Necessary
5.4 PLC Side Setting
Setting necessity at GOT connection
×
×
: As necessary ×: Not necessary
5 - 31
5