Mitsubishi Electric GOT2000 Series Connection Manual page 322

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(2) [Controller Setting] and [Ethernet] of GT Designer3
(a)
Controller setting
GOT Net No.
GOT Station
GOT Standard Ethernet Setting
GOT Communication Port No.
Retry
Startup Time
Timeout Time
Delay Time
(b)
GOT Standard Ethernet Setting
GOT IP Address
Subnet Mask
Default Gateway
Peripheral Communication Port No.
Transparent Port No.
(c)
Ethernet setting
Ethernet setting No.1
*1
*2
5 - 56
5.4 PLC Side Setting
POINT
POINT
POINT
(1) [Controller Setting] and [Ethernet] of GT Designer3
For [Controller Setting] and [Ethernet] of GT Designer3, refer to the following.
5.3.1Setting communication interface (Controller Setting)
(2) Ethernet setting
When connecting Built-in Ethernet port CPU to a GOT, the settings items for the network No.
and station No. do not exist at the PLC side. However, these virtual values must be set on the
GOT side.
Therefore, set the network No. and station No. Set the network No. that is not existed on the
network system and any station No..
Item
Item
Item
Host
N/W No.
PLC No.
Type
IP address
Port No.
Communication
Set the same value as that of GOT N/W No.
Set a value different from that of the GOT PLC No.
Set value (Use default value)
1
1
192.168.3.18
5001
3 times
3 sec
3 sec
0ms
Set value (Use default value)
192.168.3.18
255.255.255.0
0.0.0.0
5015
5014
Set value
*
*1
1
*2
2
QnUD(P)V/QnUDEH
192.168.3.39
5001
UDP (fixed)