Mitsubishi Electric GOT2000 Series Connection Manual page 752

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

■2. [Parameter Setting] of CC-Link utility
(1) Network parameter
Number of modules
Target module
Start I/O No.
Channel No.
Operation
setting
Station
information
settings
*1
*2
13 - 26
13.5 PLC Side Settings
Item
type
*1
Mode
Expanded cyclic station
Occupied number
Error event : input data status
CPU stop: data link status
Other settings
All connect count
Station type
Expanded cyclic station
*2
Occupied number
Remote station points
Reserve/invalid station select
Intelligent buffer select (word)
If the CC-Link module [Mode] is [Remote net -Ver.1 mode], [Remote station points] cannot be set.
Set the same setting as that of the GOT.
POINT
POINT
POINT
When changing the network parameter
After writing the network parameter to the C Controller module (Q Series), either turn the C
Controller module (Q Series) OFF and then ON or reset it.
Set value
1
1
0000H
(Use default value)
Master station(fixed)
Remote net (Ver.1 mode)
Single(fixed)
Exclusive station 1 (fixed)
Clear
Refresh
(Use default value)
1
Ver.1 Intelligent device station(fixed)
Single
Exclusive station 1
32 points
No setting
(Use default value)
: Necessary
: As necessary
Setting necessity
at GOT connection
: Not necessary