Mitsubishi Electric GOT2000 Series Connection Manual page 750

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

■2. Station information setting
*2
Station type
Number of stations occupied
Reserve/invalid station select
Intelligent buffer select (word)
*1
*2
■3. Completion confirmation
After initial communications of CC-Link are completed, the L RUN LED of AJ65BT-G4-S3 turns on.
The GOT starts to monitor after the L-RUN LED of AJ65BT-G4-S3 turns on.
It does not monitor while the L RUN LED turns off.
13 - 24
13.5 PLC Side Settings
*1
Item
When the [Mode] of the CC-Link module is set at [Remote net - (Ver. 2 mode)], [Remote station points] can be set.
[Remote station points] is a setting for the remote I/O station.
The default value (32 points) must be used on the GOT.
When the [Mode] of the CC-Link module is set at [Remote net - (Ver. 2 mode)] or [Remote net - Additional mode], set to [Ver. 1
Intelligent device station].
POINT
POINT
POINT
When changing the network parameter
After writing the network parameter to the PLC CPU, operate the PLC CPU ether turning OFF
and then ON or resetting.
Set value
Intelligent device
station (fixed)
Exclusive station 1 (fixed)
No setting
(Use default value)
: Necessary
PW
RUN
L RUN
SD
RD
L ERR.
Setting necessity
at GOT connection
: As necessary
: Not necessary