3.3 CC-Link System Access Range for Monitoring

When using Bus connection/CPU direct connection/computer link connection
Only connected stations can be monitored.
When using CC-Link connection (intelligent device station)
(1) Access range
The master station and local station can be monitored.
Master station (Remote network Ver.2 mode)
Local station Station No.1 (Ver.1 compatible)
Local station Station No.6 (Ver.2 compatible)
*1
Monitoring is available only when the CC-Link communication module is the GT15-J61BT13.
All devices RX, RY, RWw and RWr that are allocated to the master station by the CC-Link parameter setting can
be monitored.
When the monitor target is the multi-PLC system, CPU No. 1 to No. 4 can be monitored.
The device range of RX, RY, RWw, RWr to be allocated to the GOT differs according to the setting of the number
of CC-Link communication units (one station/four station) occupied.
For details on the number of CC-Link stations occupied, refer to the following manual .
(2) Setting device name and device number
(a) Monitoring devices RX, RY, RWw and RWr that are allocated to the master station by CC-Link parameter
setting
Use the following device names.
For devices RX, RY, RWw and RWr, designate the addresses allocated by station number setting.
• In the case of CC-Link Ver.2 (Device names to be refreshed automatically are indicated as X, Y, and D.)
Device name on PLC CPU
Input
Output
Register (write area)
Register (read area)
• In the case of CC-Link Ver.1 (Device names to be refreshed automatically are indicated as X, Y, and D.)
Device name on PLC CPU
Input
Output
Register (write area)
Register (read area)
3 - 14
3. ACCESS RANGE FOR MONITORING
3.3 CC-Link System Access Range for Monitoring
Monitor target
User's manual of the CC-Link master unit to be connected
Automatic
refresh
X
Y
D
D
Automatic
refresh
X
Y
D
D
Monitoring by cyclic transmission
*1
Device name on master
Link
station
scan
Remote input
RX
Remote output
RY
Remote register
RWw
(write area)
Remote register
RWr
(read area)
Device name on master
Link
station
scan
Remote input
RX
Remote output
RY
Remote register
RWw
(write area)
Remote register
RWr
(read area)
: Can be monitored,
: Cannot be monitored
Monitoring by transient transmission
GT Designer3 settings
Device name
Set device range
X
X0 to X1FFF
Y
Y0 to Y1FFF
Ww
Ww0 to Ww7FF
Wr
Wr0 to Wr7FF
GT Designer3 settings
Device name
Set device range
X
X0 to X7FF
Y
Y0 to Y7FF
Ww
Ww0 to WwFF
Wr
Wr0 to WrFF