5.2.5
Connection to motion controller CPU
(A273UCPU, A273UHCPU(-S3), A373UCPU(-S3))
When one GOT is connected
Extension base
Main base unit
unit
Extension cable
Main
Extension
Extension cable
base
base
Main
-
base
GT15-A370C12B(1.2m)
Extension
Main
GT15-A370C25B(2.5m)
base
base
*1
When installing the GOT 30m or more away from the main base unit, the bus connector conversion box is required.
*2
When using GT15-C EXSS-1, connect as the following precautions.
*3
When using the following functions, use GT15-ABUS(2). GT15-75ABUS(2)L cannot be used.
Used for remote personal computer operation (serial), video display function, multimedia function, operation panel function,
external I/O function, RGB display function, report function (when using a PictBridge compatible printer), hard copy function
(when using a PictBridge compatible printer), sound output function, functions with the CF card unit or CF card extension unit,
Ethernet download, gateway function or MES interface function
However, Ethernet download, gateway function and MES interface function can be used for GT16 by using the Ethernet interface.
Bus extension
connector box
Connection cable 1)
PLC
connector
Connection cable 1)
conversion
box
-
-
GT15-A370C12B(1.2m)
A7GT
GT15-A370C25B(2.5m)
-CNB
-
GT15-AC06B(0.6m)
GT15-AC12B(1.2m)
A7GT
GT15-AC30B(3m)
-CNB
GT15-AC50B(5m)
5.4.1 GT15-C [ ] EXSS-1, GT15-C [ ] BS
GOT
Connection cable 2)
Bus
Connection cable 2)
*1
GT15-A370C12B-S1(1.2m)
-
GT15-A370C25B-S1(2.5m)
GT15-C100EXSS-1(10m)
GT15-C200EXSS-1(20m)
GT15-C300EXSS-1(30m)
*2
GT15-C12NB(1.2m)
-
GT15-C30NB(3m)
GT15-C50NB(5m)
GT15-C100EXSS-1(10m)
GT15-C200EXSS-1(20m)
GT15-C300EXSS-1(30m)
*2
5. BUS CONNECTION
5.2 System Configuration
Communication driver
Bus(A/QnA)
GOT1000 Series
Max. distance
Option device
Model
*3
GT15-75ABUSL
GT15-75ABUS2L
GT15-ABUS
Between main base
GT15-ABUS2
and GOT: 2.5m
-
(Built into GOT)
GT15-75ABUSL
Between main base
GT15-75ABUS2L
and GOT: 32.5m
GT15-ABUS
(Including between
GT15-ABUS2
main base and bus
connector
conversion box)
-
Between main base
(Built into GOT)
and bus connector
conversion box:
2.5m
GT15-75ABUSL
Between main base
GT15-75ABUS2L
and GOT: 6.6m
GT15-ABUS
(Including the
GT15-ABUS2
extension cable
-
length)
(Built into GOT)
GT15-75ABUSL
Between main base
GT15-75ABUS2L
and GOT: 36.6m
GT15-ABUS
GT15-ABUS2
Between main base
and bus connector
conversion box:
6.6m
-
(Including the
(Built into GOT)
extension cable
length)
1
2
3
4
5
6
7
8
5 - 21