Connecting Freqrol-F500, F500L Series - Mitsubishi Electric GT1685 Connection Manual

Got1000 series
Table of Contents

Advertisement

15.5.3 Connecting FREQROL-F500, F500L series

Communication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating each parameter.
(1) Communication port and corresponding parameters
GOT connection destination
PU connector
FR-A5NR (Option unit)
(2) Communication settings of inverter
Set the following parameters using the PU (parameter unit). Set Pr.160 (user group read selection) to 0 [All
parameters can be accessed for reading and writing.] before making the parameter settings.
Do not change these parameters, even though they can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
Setting item
Communication station number
Communication speed
Stop bit length/data length
Stop bit length
Parity check presence/absence
Number of communication retries
Communication check time interval
Wait time setting
CRLF presence/ absence selection
Protocol selection
Operation mode selection
Link start mode selection
2
E
PROM write selection
*1
Setting items are parameter names described in the manual of FREQROL-F500 and F500L series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change the parameters on the inverter to correspond with the GOT settings.
*3
Inverter default values (No need to change)
*4
Since the value has been set as a default, no setting is required when connecting to the PU connector on the inverter side.
*5
There is no Protocol selection setting on the inverter side.
*6
The setting is required on the inverter side when FR-A5NR is used.
15 - 36
15. INVERTER CONNECTION
15.5 FREQROL Series Inverter Side Settings
Parameters corresponding to inverter
Pr.79, Pr.117 to Pr.124
Pr.79, Pr.331 to Pr.337, Pr.340 to Pr.342
Parameter No.
*1
PU connector
Pr.117
*2
Pr.118
Pr.119
*2
*2
Pr.120
Pr.121
Pr.122
Pr.123
Pr.124
*5
*6
*6
Set value
FR-A5NR
Pr.331
0 to 31
Pr.332
192
Pr.333
10
Pr.334
1
Pr.335
9999
Pr.336
9999
Pr.337
0
*3
Pr.341
1
PU
connector
Pr.79
FR-A5NR
Pr.340
1
*3
Pr.342
0
Contents of setting
15.5.14 Station number
setting
*4
19200bps
Data length: 7bit
Stop bit length: 1bit
Odd
The inverter will not come to an
alarm stop.
Communication check
suspension
0ms
With CR, without LF
1
PU operation mode
External operation mode at
*3
0
power on
Computer link operation
Written to RAM and EEPROM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents