Mitsubishi Electric GT1685 Connection Manual page 209

Got1000 series
Table of Contents

Advertisement

POINT
POINT
POINT
(1) Communication interface setting by Utility
The communication interface setting can be changed
on the Utility's [Communication Settings] after writing
[Communication Settings] of project data.
For details on the Utility, refer to the following manual.
GT
User's Manual
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
(3) When changing Stage No. and Slot No.
Change these settings with the PLC CPU turned
OFF, and then reapply the power to the PLC CPU
and GOT.
Failure to do so may generate a system alarm
(No.487).
HINT
HINT
HINT
Cutting the portion of multiple connection of the
controller
By setting GOT internal device, GOT can cut the
portion of multiple connection of the controller. For
example, faulty station that has communication
timeout can be cut from the system.
For details of the setting contents of GOT internal
device, refer to the following manual.
GT Designer3 Version Screen Design Manual
(Fundamentals)
Setting Stage No. and Slot No.
POINT
POINT
POINT
Before setting Stage No. and Slot No.
The PLC CPU recognizes the GOT as follows.
• QCPU (Q mode)
: Intelligent function module of 16 I/O points
• Other than QCPU (Q mode)
: Intelligent function module of 32 I/O points
At the [Detail setting], assign the GOT to an empty I/O
slot on the PLC CPU.
(1) When connecting to QCPU (Q mode)
Set an additional stage (16 points
connection, and assign a GOT to one of the I/O slots.
(The GOT cannot be assigned to empty slots of the
main base unit or extension base unit.)
Main base unit
Q312B
Disconnect the
Extension base unit
faulty station
Q68B
Stage No.
Slot No.
POINT
POINT
POINT
When using the bus extension connector box
Set the Stage No. switch on the bus extension
connector box to the same Stage No. as the GOT.
For setting details, refer to the following manual:
Extension
stage 1
Stage No. setting
connector
:2
Stage No.
:2
Stage No.
:0
Slot No.
:1
Slot No.
A9GT-QCNB Bus Extension Connector Box
User's Manual
5. BUS CONNECTION
5.3 GOT Side Settings
1
2
3
10 slots) for GOT
4
5
6
:2
:2
7
8
5 - 33