When designing the system

When the GOT is OFF, the following currents are supplied
to the GOT from the PLC CPU side (the power supply
module on the main base unit).(The GOT does not operate
when it is OFF.)
Design the system so that the 5V DC current consumption
of the modules on the main base unit and the total current
consumption of the GOTs will not exceed the rated output
current of 5V DC of the power supply module in use.
When connecting to
When connecting to
QCPU (Q mode)
Other than QCPU (Q mode)
5.4.9
When assigning GOT I/O
signals
Do not use the I/O signals assigned to the PLC CPU in
sequence programs, as these signals are used by the GOT
system.
When these signals are used, GOT functions cannot be
assured.
5.4.10 When connecting to a QCPU
(Q mode)
(1) Restrictions in overall cable length to No. of GOTs
The following restrictions apply when 3 of more GOTs
are connected:
Number
Overall Cable
Restriction
of GOTs
Length
1
2
Less than
3
25m
Less than
(No
4
20m
restrictions)
Less than
5
15m
(2) When using a Q00JCPU, Q00UJCPU
The bus extension connector box can be connected
only to the extension base unit.
(Connecting it to the main base unit is not allowed)
Q00JCPU,
Q00UJCPU
5 - 38
5. BUS CONNECTION
5.4 Precautions
Total current
No. of GOTs
consumption
5
2200mA
4
1760mA
3
1320mA
2
880mA
1
440mA
3
360mA
2
240mA
1
120mA
Overall Cable
Restriction
Length
(No restrictions)
Use the same
25 to 37m
power supply for
the PLC and all
20 to 37m
GOTs, and turn
these devices
ON and OFF
15 to 37m
simultaneously.
(3) When using a Q00J/Q00UJ/Q00/Q00U/Q01/Q01U/
Q02UCPU
When a GOT is bus-connected to a Q00JCPU or
Q00UJCPU, number of extension stages including the
GOT must be 2 or less.
When a GOT is bus-connected to a Q00CPU,
Q00UCPU, Q01CPU, Q01UCPU or Q02UCPU,
number of extension stages including the GOT must be
4 or less.
Main base unit
Q00JCPU, Q00UJCPU
Extension base unit
GOT
Stage No. :2
Main base unit
Q00CPU, Q00UCPU, Q01CPU,
Q01UCPU, Q02UCPU
Extension base unit
GOT
Stage No. :4
Extension
stage 1
Stage No. setting
connector
Extension
stage 1
Extension
stage 2
Extension
stage 3
Stage No. setting