Mitsubishi Electric GT1685 Connection Manual page 464

Got1000 series
Table of Contents

Advertisement

Parameter setting (when connecting to C
Controller module (Q Series))
Use SW3PVC-CCPU-E Ver.3.05F or later for the CC-
Link utility.
(1) Connection settings
Item
*1
Target module
Write authority
*2
User name
*2
Password
Detailed settings
: Necessary
*1
If the IP address of the C Controller module (Q Series) has
been changed, input the changed IP address or host name.
*2
If the account of the C Controller module (Q Series) has
been changed, input the changed user name and password.
13 - 24
13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
Setting
Set value
necessity at
GOT connection
192.168.3.3 (Default)
Mark the checkbox
target
password
-
: As necessary
: Not necessary
(2) CC-Link Utility's [Parameter Settings]
(a) Parameter settings
*1
Item
Number of modules
Target module
Start I/O No.
Channel No.
Type
Mode
Expanded cyclic setting
Occupied number
Error event: input data
status
CPU stop: data link status
Other settings
All connect count
Sta.
Station Type
No.1
Sta.
*2
Occupied number
No.1
Reserve/invalid
Sta.
station select
No.1
Intelligent buffer select
(word)
: Necessary
*1
When the [Mode] of the CC-Link module is set at [Remote
net - (Ver. 1 mode)], [Remote station points] cannot be set.
*2
Set the same number of occupied stations as that on the
GOT.
POINT
POINT
POINT
When changing the network parameter
After writing the network parameter to the C Controller
module (Q Series), either turn the C Controller module
(Q Series) OFF and then ON or reset it.
Setting
necessity at
Set value
GOT
connection
1
1
0000
H
(Use default value)
Master station (fixed)
Remote net
(Ver.1 mode)
Single
Exclusive station 1
Clear
Refresh
(Use default value)
1
Intelligent device
station
Exclusive station 1
No setting
(Use default value)
: As necessary
: Not necessary