Connecting To Melsec-L Series With Cc-Link Ver.1 Compatible; Connecting To Melsec-L Series With Cc-Link Ver.2 Compatible - Mitsubishi Electric GT1685 Connection Manual

Got1000 series
Table of Contents

Advertisement

13.4.8 Connecting to MELSEC-L
series with CC-Link Ver.1
compatible
This section describes the settings of the GOT and
MELSEC-L in the following case of the system
configuration.
POINT
POINT
POINT
(1) CC-Link module (L Series)
For details of the CC-Link module (L Series), refer
to the following manual.
MELSEC-L CC-Link System Master/Local
Module User's Manual
(2) CC-Link function built-in CPU
For details on the CC-Link function built-in CPU,
refer to the following manual.
MELSEC-L CC-Link System Master/Local
Module User's Manual
System configuration
(Example when using CC-Link module (L Series))
■ [Controller Setting] of GT Designer3
*1
<CC-Link module>
(Use the default value for the settings other than the following.)
Type
: Master station
Station No.
: Station No.0
Mode
: Remote net (Ver.1 mode)
All connect count
: 1
Transmission speed : 156kbps
■ [Network parameter] of GX Developer
<GOT>
(Use the default value for settings other
than the following.)
Station No.
: Station No.1
Expanded cyclic setting : Single
Number of
: Exclusive station
stations occupied
Transmission speed
: 156kbps
13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
[Network parameter] of GX Developer
(1) Network parameter
Item
No. of boards in module
*1
Start I/O No.
Operation setting
(Use default value)
Type
Master station (fixed)
Mode
All connect count
Remote input (RX)
Remote output (RY)
Remote register (RWr)
Remote register (RWw)
Special relay (SB)
Special register (SW)
Retry count
Automatic reconnection
station count
Stand by master station No.
(Use default value)
PLC down select
Scan mode setting
Delay information setting
Station information setting
Remote device station initial
setting
(Use default value)
Interrupt setting
: Necessary
*1
Set the Start I/O No. of the CC-Link module according to the
system configuration.
13.4 PLC Side Setting
Setting
necessity at
Set value
GOT
connection
1
0000
H
Remote net
(Ver.1 mode)
1
X400
Y400
D300
D200
SB0
SW0
Refer to (2)
: As necessary
: Not necessary
13 - 33