Connecting To Built-In Ethernet Port Cpu (Multiple Connection) - Mitsubishi Electric GT1685 Connection Manual

Got1000 series
Table of Contents

Advertisement

8.4.6
Connecting to Built-in Ethernet
port CPU (multiple connection)
This section describes the settings of the GOT and Built-in
Ethernet port CPU in the following case of system
configuration.
POINT
POINT
POINT
Connecting to Built-in Ethernet port CPU
For details of Built-in Ethernet port CPU, refer to the
following manual.
QnUCPU User's Manual (Communication via
Built-in Ethernet Port)
MELSEC-L CPU Module User's Manual (Built-
In Ethernet Function)
System configuration
[Controller Setting] and [Ethernet] of GT
Designer3
<Connecting to Built-in Ethernet port CPU>
2
(The settings other than the following are
set to the default)
Network No.
PLC No.
IP address
Port No.
Communication
format
[Q parameter setting] or [L parameter
setting] for GX Developer
*1
These setting items do not exist at the PLC side. However,
the virtual values must be set on the GOT side.
[Controller Setting] and [Ethernet] of GT Designer3
<GOT>
(The settings other than the
following are set to the default)
Network No.
: 1
PLC No.
: 1
IP address
: 192.168.0.18
Port No.
: 5001
Communication
: UDP(fixed)
format
<Connecting to Built-in
1
Ethernet port CPU>
(The settings other than the
following are set to the default)
*1
Network No.
: 1 (virtual)
*1
PLC No.
: 2 (virtual)
IP address
: 192.168.0.1
Port No.
: 5006(fixed)
Communication
: UDP(fixed)
format
: 1 (virtual)
*1
: 3 (virtual)
*1
: 192.168.0.2
: 5006(fixed)
: UDP(fixed)
[Q parameter setting] or [L parameter setting]
for GX Developer
(1) Built-in Ethernet port
Example: [Q parameter setting] screen
Item
IP address
Subnet mask pattern
Default router IP address
Communication data code
Enable online change
(FTP, MC protocol)
Disable direct connection
(Use default value)
to MELSOFT
Do not respond to search
for CPU (Built-in Ethernet
port) on network
Open settings
FTP settings
(Use default value)
Time settings
: Necessary
8. ETHERNET CONNECTION
8.4 PLC Side Setting
Setting
necessity at
Set value
GOT
connection
192.168.0.1
-
-
Refer to (2).
: As necessary
: Not necessary
8 - 33