Confirming the communication state of
Ethernet module
(1) When using the Command Prompt of Windows
Execute a Ping command at the Command Prompt of
Windows
.
(a) When normal communication
C:\>Ping 192.168.3.19
Reply from 192.168.3.19: bytes=32 time<1ms
TTL=64
(b) When abnormal communication
C:\>Ping 192.168.3.19
Request timed out.
(2) When abnormal communication
At abnormal communication, check the following and
execute the Ping command again.
• Mounting condition of Ethernet communication unit
• Cable connecting condition
• Confirmation of switch and network parameter setting
• Operation state of PLC CPU (faulty or not)
• IP address of the Ethernet module specified by Ping
command
POINT
POINT
POINT
Ethernet diagnostics of GX Works3
Ethernet diagnostics of GX Works3 is available to a
Ping test from the PLC.
For details of Ethernet diagnostics of GX Developer,
refer to the following manual.
Manuals of MELSEC iQ-R Series
8.4.4
Connection to C Controller
module (MELSEC iQ-R
Series)
.
This section describes the settings of the GOT and C
Controller module (MELSEC iQ-R Series) in the following
case of system configuration.
Use CW Configurator for the C Controller module
(MELSEC iQ-R Series) communication settings.
POINT
POINT
POINT
C Controller module (MELSEC iQ-R Series)
For details of C Controller module (MELSEC iQ-R
Series), refer to the following manual.
Manuals of C Controller module (MELSEC iQ-R
Series)
System configuration
*1
These setting items do not exist at the PLC side. However,
the virtual values must be set on the GOT side.
8. ETHERNET CONNECTION
[Controller Setting] and [Ethernet] of GT
Designer3
<GOT>
(The settings other than the
following are set to the default)
Network No.
: 1
PLC No.
: 1
IP address
: 192.168.0.18
Port No.
: 5001
Communication
: UDP(fixed)
format
<C Controller module
1
(MELSEC iQ-R Series)>
(The settings other than the
following are set to the default)
Network No.
: 1 (virtual)
PLC No.
: 2 (virtual)
IP address
: 192.168.0.3
Port No.
: 5006(fixed)
Communication
: UDP(fixed)
format
<C Controller module
2
(MELSEC iQ-R Series)>
(The settings other than the
following are set to the default)
Network No.
: 1 (virtual)
*1
PLC No.
: 3 (virtual)
*1
IP address
: 192.168.0.4
Port No.
: 5006(fixed)
: UDP(fixed)
Communication
format
■ [Module parameter] of CW Configurator
■ [Controller Setting] and [Ethernet] of GT
Designer3
8.4 PLC Side Setting
1
2
3
4
5
*1
*1
6
7
8
8 - 29