No.
Parameter
3
p9601.0
p9801.0
4
p9602 = 1
p9802 = 1
5
p9652 > 0
p9852 > 0
6
p9620 = "Value"
Terminal "EP"
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Enable "Safe Torque Off" function.
STO via Control Unit terminals
STO via Motor Module terminals
The parameters are not changed until safety commissioning mode has been exited
(i.e. when p0010 ≠ 95 is set).
Both parameters are included in the data cross-check and must, therefore, be
identical.
Enable the "Safe brake control" function.
Enable "SBC" on the Control Unit
Enable "SBC" on the Motor Module
The parameters are not changed until safety commissioning mode has been exited
(i.e. when p0010 ≠ 95 is set).
Both parameters are included in the data cross-check and must, therefore, be
identical.
The "safe brake control" function is not activated until at least one safety monitoring
function has been enabled
(i.e. p9601 = p9801 ≠ 0).
Enable "Safe Stop 1" function.
Enable "SS1" on the Control Unit
Enable "SS1" on the Motor Module
The parameters are not changed until safety commissioning mode has been exited
(i.e. when p0010 ≠ 95 is set).
Both parameters are included in the data cross-check and must, therefore, be
identical.
The "Safe Stop 1" function is not activated until at least one safety monitoring function
has been enabled (i.e. p9601 = p9801 ≠ 0).
Set terminals for "Safe Torque Off (STO)".
Set the signal source for STO on the Control Unit.
Wire terminal "EP" (enable pulses) on the Motor Module.
Control Unit monitoring channel:
By appropriately interconnecting BI: p9620 for the individual drives, the following is
possible:
Selecting/deselecting the STO
Grouping the terminals for STO
Motor Module monitoring channel:
By wiring the "EP" terminal accordingly on the individual Motor Modules, the following
is possible:
Selecting/deselecting the STO
Grouping the terminals for STO
Note:
The STO terminals must be grouped identically in both monitoring channels.
9.9 Commissioning the "STO", "SBC" and "SS1" functions
Description/comments
Safety Integrated basic functions
481