Communication
10.1 Communication according to PROFIdrive
Error
value
0x06
Illegal set operation (only reset
allowed)
0x07
Description element cannot be
changed
0x09
No description data
0x10
Read job will not be executed
0x0B
No operating priority
0x0F
No text array exists
0x11
Request cannot be executed due to
operating status
0x14
Illegal value
0x15
Response too long
0x16
Illegal parameter address
0x17
Illegal format
0x18
No. of values inconsistent
0x19
Drive object does not exist
0x65
Presently deactivated.
0x6B
Parameter %s [%s]: no write access
for the enabled controller
0x6C
Parameter %s [%s]: unit unknown
0x6D
Parameter %s [%s]: Write access
only in the commissioning state,
encoder (p0010 = 4).
0x6E
Parameter %s [%s]: Write access
only in the commissioning state,
motor (p0010 = 3).
0x6F
Parameter %s [%s]: Write access
only in the commissioning state,
power unit (p0010 = 2).
0x70
Parameter %s [%s]: Write access
only in the quick commissioning
mode (p0010 = 1).
0x71
Parameter %s [%s]: Write access
only in the ready mode (p0010 = 0).
586
Meaning
Modification access with a value not equal to 0 in a case
where this is not allowed.
Modification access to a description element which cannot
be changed.
Access to a description which does not exist (the
parameter value exists).
The read request is refused because know-how protection
is active.
Modification access with no operating priority.
Access to a text array which does not exist (the parameter
value exists).
Access is not possible temporarily for unspecified reasons. –
Modification access with a value which is within the limits
but which is illegal for other permanent reasons
(parameter with defined individual values).
The length of the present response exceeds the maximum
transfer length.
Impermissible or unsupported value for attribute, number
of elements, parameter number, subindex or a
combination of these.
Write request: illegal or unsupported parameter data
format
Write request: a mismatch exists between the number of
values in the parameter data and the number of elements
in the parameter address.
You have attempted to access a drive object that does not
exist.
You have tried to access a parameter that, although
available, does not currently perform a function
(e.g., n control set and access to a U/f control parameter).
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Remark
Additional
info
Subindex
Subindex
Subindex
Drive functions