Pulse number correction for faults

Interference currents or other EMC faults can falsify encoder evaluation. However, it is
possible to correct the measured signals using the zero marks.
Commissioning
● Set p0437.2 = 1 to activate "Pulse number correction for faults".
● Define the permissible tolerance (encoder pulses) for the zero mark distance (p4680).
● Define the limits of the tolerance window, up to which the drive corrects the pulse number
● Using p4686, define the minimum zero mark length.
Principle of operation
● This function completely corrects encoder pulse errors up to the tolerance window
● Using p4686, set the minimum zero mark length. With a factory setting of 1, it is
● Zero mark deviations of less than the minimum zero mark length (p4686) are not
● A permanently failed zero mark is indicated using the fault F3x101 "Encoder x: Zero mark
x = encoder number (x = 1, 2 or 3)
1)
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
(p4681, p4682).
(p4681, p4682) between two zero marks. The rate of correction is ¼ encoder pulses per
current controller clock cycle. As a consequence, it is possible to continually compensate
for missing encoder pulses (for example, if the encoder disk is dirty). Using the two
parameters, set the tolerance for the deviating pulse number.
If the deviation exceeds the tolerance window size, fault F3x131
Note
When the function "Commutation with zero mark" (p0404.15 = 1) is activated, then the
system waits until fine synchronization has been completed before making a correction
(r1992.8 = 1).
The pole position for the commutation is also corrected. To do this, you do not have to
activate pole position adaptation (p0430.22 = 1).
This function does not make any corrections in the speed sensing.
prevented that EMC faults result in a zero mark error.
Shorter zero marks are only suppressed when "Zero mark edge detection" is
parameterized (p0437.1 = 1).
corrected.
failed"
or the alarm A3x401
1)
"Alarm threshold zero mark failed".
1)
Basic functions
6.18 Tolerant encoder monitoring
is output.
1)
281