Siemens Sinamics S120 Function Manual page 619

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Settings in HW Config
Based on the example of the project below, the settings in HW Config are described when
using standard telegrams.
Figure 10-28 Example project of a PROFIBUS network in HW Config
Procedure
1. You have generated a project, e.g. with SIMATIC Manager and HW Config. In the project
2. Select the CU320-2 DP Control Unit as slave.
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
example, you have defined a CPU 314 controller as master and two SINAMICS S120
Control Units as slaves. For the slaves, one CU320-2 DP is intended as Publisher and
one CU310-2 DP as Subscriber.
10.2 Communication via PROFIBUS DP
Communication
617