Setpoint Settings - Set-Point Temperature For Heat Protection (°C); Setpoint Settings - Display Indicates; Setpoint Settings - Send Current Setpoint; Setpoint Settings - Cyclic Sending Of The Current Set-Point Temperature (Min) - ABB i-bus KNX Product Manual

Room temperature controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

11.5.89 Setpoint settings — Set-point temperature for heat protection (°C)
Options:
Function for protecting the building against heat. On devices with a display, this mode is
indicated by the heat protection icon. Manual operation is blocked.
Note
This parameter is only available when the "Control function" parameter is set on
"Cooling", "Cooling with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages".
11.5.90 Setpoint settings — Display indicates
Options:
The display can indicate either the absolute or relative setpoint value.
Current setpoint : On devices with a display, the setpoint is shown as an absolute
temperature, e.g. 21.0°C.
Relative setpoint : On devices with display, the setpoint is indicated as a relative value, e.g. -
5°C .. + 5°C.
11.5.91 Setpoint settings — Send current setpoint
Options:
The current setpoint value can be sent to the bus either cyclically and after a change, or only
after a change.
11.5.92 Setpoint settings — Cyclic sending of the current set-point temperature (min)
Options:
This parameter is used to specify the amount of time that will elapse before the current setpoint
value is automatically transmitted.
Note
This parameter is only available when the "Send current setpoint" is set on "Only
during change".
Product manual 2CKA001473B9482
Description of application and parameters
Setting option between 27 - 45
Current setpoint
Relative setpoint
Cyclic and during change
Only for change
Setting option between 5 - 240
Application "Function block RTC"