Basic Stage Heating - Control Value Difference For Sending Of Heating Control Value; Basic Stage Heating - Cyclic Sending Of The Control Value (Min); Basic Stage Heating - Pwm Cycle Heating (Min) - ABB i-bus KNX Product Manual

Room temperature controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

11.5.23 Basic stage heating — Control value difference for sending of heating control value
Options:
The control values of the 0 - 100% PI continuous controller are not transmitted after every
calculation. Instead, they are transmitted when the calculation results in a value that is different
enough to the previous sent value to make a transmission meaningful. This value difference can
be entered here.
Note
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%", "PI PWM, On/Off" or "Fan coil".
11.5.24 Basic stage heating — Cyclic sending of the control value (min)
Options:
The current control value used by the device can be cyclically transmitted to the bus.
Note
This parameter is only available when the "Control value type" parameter is set
either on "2-point 1 Bit, Off/On", "2-point 1 Byte, 0/100%", "PI continuous, 0-
100%" or "Fan coil".
11.5.25 Basic stage heating — PWM cycle heating (min)
Options:
In PI PWM, On/off the control value percentage values are converted into a pulse-interval
signal. This means that a selected PWM cycle will be divided into an on-phase and an off-phase
based on the control value. Accordingly, a control value output of 33% in a PWM cycle of 15
min. results in an "On-phase" of five minutes and an "Off-phase" of 10 min. The time for a PWM
cycle can be specified here.
Note
This parameter is only available when the "Control value type" parameter is set
on "PI PWM, On/Off".
Product manual 2CKA001473B9482
Description of application and parameters
2 %
5 %
10 %
Send cyclic only
Setting option between 1 - 60 minutes
Setting option between 1 - 60 minutes
Application "Function block RTC"