Object Type Actuator Group X; Scene Number - ABB i-bus KNX Product Manual

Room temperature controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

11.6.9.6

Object type actuator group x

Options:
1-bit switching:
The value is sent as 1-bit switching commands (0 or 1), e.g. On/Off, enabled/blocked,
true/untrue.
1-bit blind:
The value is sent as 1-bit switching commands, e.g. travel up or down.
1 byte 0 - 100%:
The value is sent as 1-byte value without a sign (percentage value).
(0 = 0%, 255 = 100%)
Temperature:
The value is sent as 2-byte floating point value (-671088.6 - 670760.9).
The parameter is used to set the bit size of communication object "GFx: actuator group x" for
different applications.
11.6.9.7

Scene number

Options:
The parameter is used to specify which light scene is to be started.
Product manual 2CKA001473B9482
Description of application and parameters
Number of light scene
1-bit switching
1-bit blind
1 byte 0 - 100%
Temperature
Setting option from 1 to 64
Application "General functions"
│174