Enable Object After Return Of Voltage; Cyclic Sending - ABB i-bus KNX Product Manual

Room temperature controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

11.6.2.6

Enable object after return of voltage

Options:
Blocked:
Object "GFx: enable" is not activated at bus voltage recovery. The blocking function is
deactivated.
Enabled:
If object "GFx: enable" was activated prior to bus voltage recovery, it will also be
activated after bus voltage recovery.
The parameter serves to ensure that a defined value is present on communication object "GFx:
enable" after a return of bus voltage.
Note
This parameter can only be set if the "Enable object" parameter is set on
"activated".
11.6.2.7

Cyclic sending

Options:
Always activated:
Telegrams that are received on object "GFx: input" are transferred directly to object
"GFx: output" and there sent cyclic.
Activated at a specified value:
This value is sent cyclic via object "GFx: output" only at the receipt of a specific, set
value. If a different value is received on "GFx: input", no telegram is sent via object
"GFx: output".
Activated except at a specified value:
This deviating value is sent cyclic via object "GFx: output" only at the receipt of a value
that deviates from the set value.
Product manual 2CKA001473B9482
Description of application and parameters
Blocked
Enabled
Always activated
Activated at a specified value
Activated except at a specified value
Application "General functions"
│144