Rtc - General; General - Device Function; General - Overwrite Local Setting At Download - ABB i-bus KNX Product Manual

Room temperature controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

11.5.5

RTC - General

11.5.6
General — Device function
Options:
Single device
The device is used individually in a room for temperature control with fixed temperature
values.
Master device:
At least two room temperature controllers are located in one room. One device must be
set up as a master device, while the others must be programmed as slave devices. The
master device must be linked to the slave devices using the appropriately labelled
communication objects. The master device regulates the temperature.
Slave device:
The device only sends the measured temperature to the KNX bus.
11.5.7

General - Overwrite local setting at download

Options:
Deactivated:
Manual settings are not overwritten during a download.
Activated:
All parameters are reset to the values that were fixed in the commissioning software.
The parameter is used to specify whether the settings that were made on the device by the user
are overwritten during a download
Product manual 2CKA001473B9482
Description of application and parameters
Single device
Master device
Slave device
Deactivated
Activated
Application "Function block RTC"