11.5.19 Basic stage heating
Note
Only available when the "Extended settings" parameter under "Heating control"
is set on "Yes".
11.5.20 Basic stage heating — Status object heating
Options:
–
This parameter enables the "Status heating" communication object.
11.5.21 Basic stage heating — Mode of the control value
Options:
The mode of the control value can be used to adapt the control value to de-energised opened
(normal) or de-energised closed (inverse) valves.
–
N ormal : Value 0 means "Valve closed".
–
Inverse : Value 0 means "Valve open".
11.5.22 Basic stage heating — Hysteresis (x 0.1°C)
Options:
The hysteresis of the two-point controller specifies the fluctuation range of the controller around
the setpoint value. The lower switching point is located at "Setpoint value minus hysteresis" and
the upper point is at "Setpoint value plus hysteresis".
Note
This parameter is only available when the "Control value type" parameter is set
either on "2-point 1 Bit, Off/On" or "2-point 1 Byte, 0/100%".
Product manual 2CKA001473B9482
Description of application and parameters
No
Yes
Normal
Inverse
Setting option between 3 - 255
Application "Function block RTC"
│84