11.5.138.2

Object type for status object

Options:
1 bit:
The value is sent as 1-bit switching commands (On/Off) and the button LEDs light up in
the colour for On or Off.
1 byte 0 - 100%:
The value is sent as 1-byte value (percent) and the button LEDs light up in the colour for
the associated zone (1 - 5).
The parameter is used to set the size of communication objects for the colour of the LED.
For selection "1 bit", the 1-bit object "Status LED" is available. If an On telegram is received via
the object, the RTC button LEDs light up in the colour that is stored in the "Colour for On"
parameter. If an OFF telegram is received via the object, the LEDs light up in the colour that is
stored in the "Colour for Off" parameter. The LEDs can also be switched off.
For selection "1 byte 0-100%", the 1-byte object "Status LED" is available. If a value telegram is
received via the object, the RTC button LEDs light up in the colour that is set in the "Colour for
zone" parameter. The LEDs can also be switched off for each zone.
The five adjustable zones have the following behaviour:
Zone 1: 0%
Zone 2: 1% ≤ value < S1
Zone 3: S1 ≤ value < S2
Zone 4: S2 ≤ value ≤ 99%
Zone 5: 100%
The threshold value for S1 is set via the parameter "Threshold between Zone 2 and 3" (%).
The threshold value for S2 is set via the parameter "Threshold between Zone 3 and 4" (%).
Note
The parameter is only adjustable if the "Operating mode" parameter is set on
"Status illumination".
Product manual 2CKA001473B9482
Description of application and parameters
1 bit
1 byte 0 - 100%
Application "Function block RTC"