11.5.2.2
Setting the temperature unit via object
Options:
No:
■
–
Communication object "HMI: units switchover" is not enabled.
Yes:
■
–
Communication object "HMI: units switchover" is enabled.
–
If a telegram with value "1" is received via the object, the temperature is displayed in °C.
If a telegram is received with value "0"; the temperature is displayed in °F.
The parameter is used to specify whether the 1-bit communication object "HMI: units
switchover" is set.
11.5.2.3
Display of the actual temperature
Options:
No:
■
–
The actual temperature is not displayed after the waiting period.
Yes:
■
–
The actual temperature is displayed after the waiting period.
The parameter is used to specify whether the actual temperature is shown in the display as
priority. This means that when the device is not operated within the set waiting period, the
current actual temperature is shown in the display.
Product manual 2CKA001473B9482
Description of application and parameters
No
Yes
No
Yes
Application "Function block RTC"