11.6.4

Application - Logic gate

Up to ten input values can be linked with each other via the application.
The following communication objects are available:
"GFx: output"
"GFx: input x"
All input objects and the output object can take on size 1 bit or 1 byte independent from each
other.
The application is used to specify the logic gate the enabled input objects are linked with. At the
receipt of new telegrams at the inputs, they are switched according to the selected function. The
inputs can also be individually inverted.
The result determined from the inputs is sent via the output object. The default value that is to
be sent at a positive result can be adjusted.
Note
The parameters for application "Logic gate" can be called via general
parameters, parameter input x and output parameters .
Note
The number of the object (GF1 - GFx) depends on the channel used.
11.6.4.1

Channel name

Entry:
The parameter can be used to name the selected channel. The preset name "Channel" can be
replaced with any arbitrary name. The length of the name is limited to 30 characters.
Product manual 2CKA001473B9482
Description of application and parameters
<Name>
Application "General functions"
│147