NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
SNMP Port is set to 161 by default.
If you modify SNMP Port and tap Submit, a warning is displayed, indicating that the
monitoring system will restart, as shown in
Figure 5-16 Changing an SNMP port
Step 6 Tap Next Page.
Step 7 Set SNMP trap parameters.
1.
2.
Trap Port is set to 162 by default.
3.
4.
5.
----End
Issue 10 (2019-01-15)
Tap Add under SNMP Trap.
Set Trap Address as planned and Trap Port to the actual port number.
Select the SNMP Version. If an SNMPv3 user is configured, it is recommended that
SNMP Version be set to SNMPv3.
If SNMP Version is set to SNMPv3, select an SNMPv3 user name, and then tap
as shown in
Figure
5-17.
Figure 5-17 Setting SNMP trap parameters
Tap Submit under SNMP Trap.
Copyright © Huawei Technologies Co., Ltd.
Figure
5-16.
5 ACC Introduction
,
99