The following figures show the infrared humidifier structure and its components.
Figure 6-1 NetCol8000-A050 infrared humidifier structure
(1) Water inlet
(4) Infrared
Issue 10 (2019-01-15)
Operations
Check that the water pan drains water
properly.
Check the scale status of the infrared
humidifier water pan. Clean the water pan
and Y-shaped strainer if there are any
scales. The cleaning procedures are as
follows:
1. Close the inlet valve.
2. Remove the self-overflow vent to drain
water out, and disconnect the drainpipe.
3. Take away the wires to the temperature
switches for dry heating protection.
4. Refer to
6.4.4 Replacing the Infrared
Humidifier Lamps
to remove and clean
the water pan.
5. Fix the filter port using a wrench (as
shown by 1 in
Figure
filter using the wrench (as shown by 2 in
Figure
6-3) and clean the Y-shaped
strainer using a brush.
6. Clean up dirt in the water pan with a
hard brush and detergent, and wash the
water pan with water.
7. Install the water pan in reverse order.
(2) Ceramic lamp holder
(5) Topside overheat
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Troubleshootin
g
there are
blockages.
Close the main
humidifier water
inlet. Clean the
foreign matters in
the water pan.
N/A
6-3) remove the
Remarks
Perform the
operations
with the
power on.
Perform the
operations
with the
power off.
(3) Water pan
(6) Manual reset temperature
139