5.4.6 Setting Communications Parameters (SNMP Settings)

Context
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > SNMP Settings.
displayed.
Issue 10 (2019-01-15)
Setting
Enable,
Disable
Enable,
Disable
N/A
N/A
To set communications parameters, log in as the Admin or Engineer user.
This section is suitable only for SNMP. Skip this section if you use Modbus.
Record the values entered in this section. They will be used when you access a smart
cooling product to an EMS (element management system).
One smart cooling product supports concurrent access of up to 10 EMSs through SNMP.
Copyright © Huawei Technologies Co., Ltd.
Setting Method
establish communication.
If you set Link mode to Server and client, the smart
cooling product, as a server, supports two client
connection and establishes communication. In
addition, the smart cooling product, as a client, can
connect to a remote server and establish
communication.
This parameter is configurable when Link mode is set
to Client.
This parameter is configurable when Link mode is set to
Server.
Enter the actual IP address of the EMS. IP addresses of
the display panel, EMS client, and EMS server must be
unique. This parameter is configurable when Link mode
is set to Client.
It is recommended that you retain the default value. If you
need to change the value, enter a value as required. This
parameter is configurable when Link mode is set to
Client.