NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
Figure 3-58 Removing the sheet metals for transporting the compressor
Step 2 Tighten the bolts with torque of 15 N•m.
----End
3.8 Installation Verification
Indoor Unit Installation Verification
After installing an indoor unit, check the components listed in the following table.
Table 3-14 Check items on the indoor unit installation
Check Item
Cabinet
Electric
heater
Infrared
humidifier
Issue 10 (2019-01-15)
Put away the removed sheet metals so that you can reinstall them if the indoor unit is to be transported
again.
Expected Result
The cooling system has good air tightness.
The cabinet is installed properly, without any tilt.
The cabinet is secured to the support by using bolts.
The foreign matter inside the cabinet such as cable ties and stubs is
cleaned up.
The electrical heater is secured.
The humidifier is secured.
The protective device for the infrared humidifier is removed
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
73