Huawei NetCol8000-A Series User Manual page 162

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A Series:
Table of Contents

Advertisement

NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
Alarm
Alarm
ID
Name
a028
Power
phase A
overvolt
a029
Power
phase B
overvolt
a030
Power
phase C
overvolt
a031
Power
phase A
undervolt
a032
Power
phase B
undervolt
Issue 10 (2019-01-15)
Alarm
Occurrence
Severit
Conditions
y
generated.
Major
The AC
voltage of
phase A is
greater than
the alarm
threshold, and
the alarm
detection
delay expires.
Major
The AC
voltage of
phase B is
greater than
the alarm
threshold, and
the alarm
detection
delay expires.
Major
The AC
voltage of
phase C is
greater than
the alarm
threshold, and
the alarm
detection
delay expires.
Major
The AC
voltage of
phase A is
greater than 50
V and less
than the low
voltage alarm
threshold
when the
alarm
detection
delay expires.
Major
The AC
voltage of
phase B is
greater than 50
V and less
than the low
voltage alarm
threshold
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible Causes
1. The power supply voltage
is higher than the power
overvolt alarm thres.
2. If a voltage jumper is used,
possibly it is incorrectly
connected.
3. If a toggle switch is used,
possibly it is incorrectly
set.
1. The power supply voltage
is higher than the power
overvolt alarm thres.
2. If a voltage jumper is used,
possibly it is incorrectly
connected.
3. If a toggle switch is used,
possibly it is incorrectly
set.
1. The power supply voltage
is higher than the power
overvolt alarm thres.
2. If a voltage jumper is used,
possibly it is incorrectly
connected.
3. If a toggle switch is used,
possibly it is incorrectly
set.
1. The power supply voltage
is lower than the power
overvolt alarm thres.
2. If a voltage jumper is used,
possibly it is incorrectly
connected.
3. If a toggle switch is used,
possibly it is incorrectly
set.
1. The power supply voltage
is lower than the power
overvolt alarm thres.
2. If a voltage jumper is used,
possibly it is incorrectly
connected.
3. If a toggle switch is used,
Solutions
1. Check the power
supply voltage.
2. Maintain or replace
the voltage jumper.
3. Correctly set the
toggle switch.
1. Check the power
supply voltage.
2. Maintain or replace
the voltage jumper.
3. Correctly set the
toggle switch.
1. Check the power
supply voltage.
2. Maintain or replace
the voltage jumper.
3. Correctly set the
toggle switch.
1. Check the power
supply voltage.
2. Maintain or replace
the voltage jumper.
3. Correctly set the
toggle switch.
1. Check the power
supply voltage.
2. Maintain or replace
the voltage jumper.
3. Correctly set the
toggle switch.
153

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents