Installation Layout Principles
Layout principles for installing the NetCol8000-A:
If the outdoor unit is placed higher than the indoor unit, install an oil trap every 5 m to 6 m
along pipes in the vertical direction.
and inverted traps.
The inverted trap should be higher than the top copper pipe of the condenser in the outdoor
unit.
Issue 10 (2019-01-15)
The pipes in real line are installed by Huawei before delivery.
The pipes in dash are to be routed onsite by technical personnel.
Huawei does not provide the inverted trap (component 11) and oil traps (component 9) used in the
scenario where the outdoor unit is placed higher than the indoor unit. However, to ensure the normal
operating and easy maintenance of the NetCol8000-A, it is recommended that you use these two
components.
If the outdoor unit is placed higher than the indoor unit:
Copyright © Huawei Technologies Co., Ltd.
(8) Ball valve
(11) Inverted trap
(14) Solenoid valve
(17) Needle valve after the
thermostatic expansion
valve
(20) Indoor fan
(23) Sensing bulb
Figure 3-2
and
Table 3-7
3 Installation Guide
valve
(9) Oil trap
(12) Dry filter
(15) Sight glass
(18) Distributor
(21) Freeze point protecting
switch
(24) Low pressure needle
valve
show the parameters of oil trap