NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
Procedure
Step 1 On the home screen, tap
Step 2 Set teamwork control parameters.
You can set all the teamwork control parameters on the master smart cooling product but only
Teamwork group no., Teamwork unit address, and Teamwork function on a slave smart
cooling product, other parameters of the slave smart cooling products will be modified by the
master smart cooling product synchronously.
Table 5-6 Teamwork settings
Parameter
Teamwork
group no.
Teamwork
unit address
Teamwork
CAN
resistor
enable
Teamwork
function
Issue 10 (2019-01-15)
> Teamwork Settings.
Description
The number of the
teamwork controlled
group, which is the
same for all the devices
in the group.
Only one device in
each group can be set
to 1. Other device
addresses should be
different from each
other.
Indicates the build-out
resistor status of each
smart cooling product
in a teamwork group.
Disable or enable the
teamwork function. If
the teamwork function
is disabled, this device
is operating according
to its own control If the
teamwork function is
enabled, this device
works in harmony with
others that in the same
Copyright © Huawei Technologies Co., Ltd.
Table 5-6
describes how to set the parameters.
Configuration
Principle
Set the assigned
teamwork control
number.
Set the assigned unit
address.
Set this parameter
to No for
non-teamwork
scenarios.
For teamwork
scenarios, set this
parameter to Yes
for the first and last
smart cooling
products in a
teamwork group,
and set it to No for
other smart cooling
products.
Set this parameter
based on the onsite
device heat
distribution.
5 ACC Introduction
Default Value
1
NA
No
Disable
101