2.3.2 Environmental Requirements

Table 2-5 Environmental specifications
Parameter
Ambient humidity
Ambient temperature
Operation temperature of
cooling system
The temperature range of the
outdoor unit
Protection level
Storage temperature
Storage humidity
Altitude
Water requirements to the
humidifier
Issue 10 (2019-01-15)
Specifications
Width ≥ 0.9 m, height ≥ 2.3 m.
Bearing capacity not smaller than 350 kg/m
For raised floors, height not smaller than 400 mm (Applies to the
downflow smart cooling product).
Routing from the bottom or side.
Front and side maintenance for smart cooling products.
Front maintenance distance ≥ 800 mm, side maintenance distance ≥
600 mm.
Do not install the smart cooling product near a noise-sensitive place such as an office or a conference
room.
Copyright © Huawei Technologies Co., Ltd.
Specifications
20% RH to 80% RH.
0° C to 40° C.
18° C to 32° C.
Outdoor unit (NetCol500-A072): –20° C to + 45° C. (If
low-temperature component is used, the lowest
temperature is -40° C.)
Outdoor unit (NetCol500-A088): –20° C to + 55° C.
Indoor unit: IP20.
Outdoor unit: IPX5.
–40° C to +70° C.
5% RH to 95% RH (non-condensing).
0 m to 1000 m. The refrigerating capacity is derated
when the altitude is above 1000 m. For details, see
Table
2-6.
The sum of calcium and magnesium cannot exceed 600
mg/L.
2 Product Description
2
.
17