NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
Issue 10 (2019-01-15)
Figure 5-25 Active alarms screen
Active alarms are displayed in chronological order. The latest generated alarm is displayed in the
uppermost row.
If active alarms exist, they are displayed on the alarm bar one by one.
You can query an alarm on the alarm list in related user manual for smart cooling product based on
the alarm ID to view causes of the alarm and methods used to clear the alarm.
Click each alarm to open the Details page, which contains Alarm Name, Severity,
Location, Cause ID, SN, Possible Causes, and Procedure for the alarm, as shown in
Figure
5-26.
Figure 5-26 Details
−
If the
icon is not displayed on the Details screen, the alarm can be
automatically cleared after the fault is rectified.
−
If the
icon is displayed on the Details screen, the alarm can be manually
cleared by tapping the Clear button after the fault is rectified. The alarm clearance
type (automatic or manual) varies with smart cooling products. Some of the alarms
can either be cleared automatically or manually. Perform operations as required.
For details about how to manually clear an alarm, see
Alarms.
To query historical alarms, choose Common Functions > Query Hist. Alarms or
Alarms > Query Hist. Alarms on the home screen.
Copyright © Huawei Technologies Co., Ltd.
5 ACC Introduction
5.13 How to Manually Clear
Figure 5-27
is displayed.
111