Advertisement

NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual

5.4.6 Setting Communications Parameters (SNMP Settings)

Context
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > SNMP Settings.
5-9
Figure 5-9 Setting SNMP communications parameters
Step 2 Set SNMP Version based on site requirements, and then tap Submit.
Step 3 Set Read Community and Write Community.
1.
Issue 12 (2020-10-28)
To set communications parameters, log in as the Admin or Engineer user.
This section is suitable only for SNMP. Skip this section if you use Modbus.
Record the values entered in this section. They will be used when you access a
smart cooling product to an EMS (element management system).
One smart cooling product supports concurrent access of up to 10 EMSs
through SNMP.
is displayed.
If you set SNMP Version to ALL or SNMPv1&v2c, you can set Read
Community and Write Community. You can modify the settings by following
instructions provided in
If you set SNMP Version to ALL or SNMPv3, you can add SNMPv3 users by
performing
Step
4.
Tap the text box after Read Community, as shown in
Community as planned, tap
Copyright © Huawei Technologies Co., Ltd.
Step
3.
, and then tap Submit.
5 ACC Introduction
Figure
Figure
5-10. Set Read
101